ELECTRONICS APM300 DOOR MONITOR SYSTEM |
| |
General
- Provide and install a door monitor call system for audibly
and visually annunciating door entry at a master control panel.
The door alarms may be individually reset at the master control
panel as well as by -passed during certain hours of the day.
System Operation - Opening a door that is armed shall
provide the following indications at a master annunciator
panel: flash a specific door LED, flash a common call placed
LED, and sound an alarm tone. The alarm may be reset or by-passed
at the master annunciator panel by depressing the associated
door push button. This causes the Call Placed LED to stop
flashing, the specific door LED to illuminate continuously,
and the alarm tone to extinguish. Each door or zone has an
individual door reset/bypass push button and LED. Releasing
a reset/by-pass push button turns off the associated LED and
arms the door circuit.
Annunciator Panel - Provide a APM300 series master
annunciator having a 4-zone DM4 door sentry modules. Each
DM4 module shall have four individual door reset/bypass push
buttons with associated LEDs. The minimum system shall have
one DM4 module or four zones. The maximum capacity shall be
42 DM4 modules or 168 zones; the minimum increment is one
DM4 or four zones. This annunciator shall also contain a common
call placed LED, an alarm tone speaker and a momentary action
tone silencing push button. When activated, the tone silencing
circuitry shall automatically reset after the alarm is reset.
Each button cap on the DM4 modules) shall be marked with the
door identity. The APM300 panel (s) should be constructed
of anodized clear aluminum and shall be supplied with a recess
mounting frame.For parallel operation of master annunciators,
specify Model DM4P door sentry modules in place of the DM4
modules. The features and operation shall be identical to
the above except that either master annunciator can arm or
disarm/bypass individual doors.
Control Unit - Provide a Model FMC28/29 control unit.
It provides a volume control and jumper option for a pulsating
or steady alarm signal tones. The overall size for both control
units shall be 8.625” long x 5.562” wide x 2”
deep.
Power Supply - Provide a Model UM598TM transformer.
Door Contacts - Provide a Pacific Electronics mechanical
door or window contacts. Specify Model #92670000 (magnetic
door contacts) |
|
|
DOOR
MONITOR SYSTEM
FEATURES:
•Audible and Visual Call Indication
•Pulsating or Steady Alarm Tone
•Tone Silencing Switch with Automatically Resettable Tone
Circuitry
•Remote Alarm Reset Capability
•LED Annunciation
•Parallel Annunciation Capability
•Expandable from 4 to 168 Zones
DESCRIPTION:The Door Monitor System provides
audible and visual indications of door entry at master annunciator
panel. Calls are displayed until entry switch contacts are manually
restored and the master annunciator’s reset.
SYSTEM COMPONENTS:
Annunciator Panels
Model# / #Of Panels / Zone Capacity
APM300-1 / 1 / 4-24
APM300-2 / 2 / 28-60
APM300-3 / 3 / 64-96
APM300-4 / 4 / 100-113
APM300-5 / 5 / 136-168
Rough Opening / Frame Opening / Back Box
5.25”W / 6.125”W / BB33-1
9.125”W / 10.135”W / BB33-2
13.125”W / 14.125”W / BB33-3
17.125”W / 18.125”W / BB33-4
21.125”W / 22.125”W / BB33-5
Wall Opening Height: 16.625” Frame Overall Height: 17.812”
Depth: 4” |
| |
 |
DOOR SENTRY MODULES
DM4 4 zone door module
DM4P 4 zone door module for parallel master annunciators. |
| |
 |
CONTROL
UNIT
FMC28/29 Control Unit
|
| |
 |
MODEL#92670000
FUNCTION: For tandem usage with the door control
module Pacific catalog number 92660000, the magnetic door contact
device is designed for surface mounting at the door or window.
Door Contact specifications: Magnetic door
contact device shall be supplied in a dust free enclosure and
be applicable to all surface mounting requirements. Door contact
shall be single pole, normally open when the door is closed. |
| |
 |
TRANSFORMER
- UM598TM |
| |
COMPANY
| ELECTRONIC PRODUCTS | INTERCOM
PRODUCTS
NURSE & E-CALL PRODUCTS | CUSTOMER
LIST | CONTACT US
© 2005-2006 Pacific Electronics
All Rights Reserved |
|
| Bells |
|
| Horns |
|
| Call
of Aid Kit |
|
| Visual
Emergency Call Systems |
|
| Replacement
Parts |
|
| 730
Door Monitor System |
|
| APM300
Door Monitor System |
|
|